This section should be read in conjunction with 6 External Moisture Overview.
COP v24.09:Roofing;
The pitch is the angle between the horizontal and the roof line. It is also the relationship between the rise and the horizontal span of the roof. See 18.2 Pitch & Rise Calculator for the tabulation of these values and a calculation tool.
7.1.1A Minimum Pitch for Generic Metal Roofing
Profile | Min Height | Min Pitch | Check Capacity after run of... |
---|---|---|---|
Trapezoidal Asymmetrical | 20 | 4° | 20 m |
27 | 3° | 40 m | |
36 | 3° | 65 m | |
Trapezoidal Symmetrical | 20 | 4° | 15 m |
30 | 4° | 25 m | |
Secret Fix | 30 | 3° | 60 m |
25 | 3° | 30 m | |
Standing Seam | 30 | 3° | 85 m |
25 | 3° | 35 m | |
Corrugate | 16.5 | 8° | 15 m |
21 | 4° | 20 m | |
35 | 3° | 65 m |
Buildings designed with widely spaced purlins and widely spaced portal frames may require an increased design pitch to comply with the minimum recommended as-laid pitches.
Low pitched roofs require greater attention to flashing details. The ability of side laps or end laps to withstand water penetration also becomes more critical at low pitches, but the good design of flashings can ensure weathertightness in extreme conditions.
7.1.1B Exceptions to the Minimum Recommended Roof Cladding Pitch requirements:
- Curved roofs, where by design the minimum pitch at the crest is always less than the prescribed minimum pitch. In these cases, the pitch at the eaves must comply with the profile’s minimum pitch, and the pitch at the upper end of a terminated arc must be a minimum of 3°. (See 15.1 Curved Roofs).
- The back curbs of penetration flashings where the minimum pitch is 1.5°. (See 9 External Moisture Penetrations)
Runoff is the ability of the roof cladding to discharge maximum rainfall without water penetrating through side laps, end laps or flashings and depends on rainfall, the catchment area, the roof pitch, and the profile geometry.
The roof pitch determines the rate of flow; steep slopes shed water faster than shallow slopes. The rib height and spacing of trapezoidal profiles also affects its shedding ability.
For example: At a rainfall intensity of 200 mm/hour, a five-rib trapezoidal profile at 3°, with a rib height of 27 mm can have a run of 90 m.
The 7.1.4 Maximum Run Calculator can calculate capacities for any known profile.
The capacity of a roof profile to drain water is determined by its geometry and the roof pitch. The catchment area is the distance between rib centres times the length, and the effective cross-section area and the wetted perimeter is taken to the height of the overlap on corrugate, or capillary bead on trapezoidal and trough section profiles.
The 7.1.4 Maximum Run Calculator gives the maximum length that a roof can drain at a given pitch and rainfall intensity. The manufacturer’s data can be accessed from the drop-down box; for other profiles, the data can be entered manually into the worksheet.
Where the flow of water is concentrated by penetrations or spreaders, go to the 9.4.4 Maximum Area Above Penetration Calculator.
Before using this calculator, please read 5.3 Roof Drainage Design.
The Maximum Run Calculator calculates the maximum roof length to achieve effective roof drainage for any profile, pitch, and rainfall intensity. Insert the values in the designated fields.
For an explanation of each element, please click on the corresponding question mark.
For rainfall intensities, refer to NIWA’s HIRDS tool or the 5.3.2 Rainfall Intensity.
This address is not factored into calculations - you must determine intensity from Rainfall Intensity Maps or NIWA's HIRDS tool.
The address is not recorded or shared with any other parties.
You can increase this manually for critical applications.
Minimum Fall 1:500, Maximum Fall 1:100
Be sure to consider all relevant elements when assessing a roof area.
Be sure to consider all relevant elements when assessing a roof area.
Be sure to consider all relevant elements when assessing a roof area.
Be sure to consider all relevant elements when assessing a roof area.
Conditions and assumptions for flat gutters:
- Mannings n assumed to be 0.014 to represent long term friction conditions.
- Equations valid for gutters with min gradient 1:500, max gradient 1:100.
- Bends are accounted for by local loss coefficients (0.5 for each 90° bend).
Conditions and assumptions for downpipes:
- Mannings n assumed to be 0.014 to represent long term friction conditions
- Any grates must not restrict flow or site-specific design is to be completed - typically double the number of outlets
- Gutters must have fall for downpipe sizing to be valid
- Calculations consider weir, orifice and friction effects
- Orifice discharge coefficient of 0.61 assumed
- Weir coefficient of 0.65 and 75% of outlet perimeter assumed available for weir flow
- Minimum pipe gradient of 20% assumed for friction conditions
Conditions and assumptions for valleys:
- Mannings n assumed to be 0.014 to represent long term friction conditions
- Minimum height of Type A valley returns to be 16 mm
- Minimum freeboard of 20mm mm for valleys below 8°
- Minimum freeboard of 15mm for valleys 8° and steeper
Conditions and assumptions for maximum run:
- Mannings n assumed to be 0.014 to represent long term friction conditions
- Only valid for supercritical flow (most roofs)
Conditions and assumptions for penetrations:
- Mannings n assumed to be 0.014 to represent long term friction conditions
- Only valid for supercritical flow (most roofs)
- Where Both Sides selected, assumes an even split of flow to either side of penetration
Conditions and assumptions for level spreaders:
- Mannings n assumed to be 0.014 to represent long term friction conditions
- Only valid for supercritical flow (most roofs)
- Corrugate Profiles
- No discharge to lap row
- One discharge hole per second trough
- Assumes flow to top of profile (no freeboard)
- Trapezoidal or Trough Profiles
- May discharge to lap row
- One discharge hole per trough
- Assumes flow to capillary groove of profile
All fastenings that pierce the sheeting should be provided with adequate sealing washers to prevent leakage. Sealing washers should be made from Ethylene Propylene Diene Monomer (EPDM).
Fastenings should be tightened only enough to form a weatherproof seal without damaging the sealing washer or deforming the sheet profile. Deformed sheeting will cause water to pond around the seal.
Swarf should be removed from under the sealing washer as it will not only cause staining but also interfere with the seal.
All metal cladding and flashings are subject to expansion and contraction caused by changes in temperature, and their design should allow for this movement. The energy produced should be absorbed without damage to the cladding, fixings or structure. The recommendations in this section are specific to preventing damage and leaks through thermal movement. Thermal movement can also cause disturbing noise levels in dwellings with shorter member lengths than those recommended in this section. (See 12.1 Roof Noise.)
The ribs of metal trapezoidal or corrugated roof and wall cladding absorb expansion across the width of the sheets, but special provisions are needed over the sheets' length.
Much of the longitudinal expansion is taken up by the bowing of the sheet between fastened supports. The extent to which this happens depends on the profile strength and support spacings.
Failure by thermal expansion normally results in shearing of the fastener. Fasteners into lightweight steel purlins up to 3 mm in thickness are less vulnerable as they tend to rotate rather than be subjected to repeated bending resulting in fatigue failure. Fasteners into hot rolled steel sections or timber are far more vulnerable to this mode of failure and in all run lengths over 20 metres provision for expansion must be made when fastening into such supports.
Where overlapping sheets are fastened through the ends, they must be considered as one length to calculate thermal movement. Unfastened end laps are not recommended.
Wall cladding does not require the same provisions as roof cladding, because of solar radiation angle.
Oversized holes and washers give some room for expansion and contraction, but it is not enough to allow movement without stress or distortion over long spans. In such cases, a step joint should be used. (See 8.5.5.3B Stepped Roof Flashing)
7.3.1A Steel Cladding Temperature Ranges
Max/Min Roof Temp °C | No Wind | |||
Insulated | Light colour | +60° -15° | = | 75° |
Insulated | Dark colour | +80° -15° | = | 95° |
Uninsulated | Light colour | +50° -10° | = | 60° |
Uninsulated | Dark colour | +65° -10° | = | 75° |
Aluminium and zinc, which have twice the expansion rate of steel, do not necessarily expand to this degree because of the different characteristics of mass, emittance, and radiance which affects their temperature range. Copper expands one and a half times as much as steel, and stainless steel can expand up to 1.5 times as much as steel depending on composition.
The theoretical expansion of steel roof cladding in mm is 12 x temperature change x length in metres/1000.
Steel expansion rates can be calculated as follows:
Given a length (e.g., 30 m) and that the material (e.g., a light-coloured uninsulated roof) moves through a 60°C range (e.g., + 50°C -10°C), the theoretical increase in length is 12 x 60 x 30/1000 = 21.6 mm.
This amount of movement of roof cladding and components does not have to be provided for in practice, because:
- The building also expands with the ambient temperature, although to a lesser degree.
- Fasteners into light gauge purlins will roll rather than bend. The purlin flange may also roll to a degree.
- The roof cladding bows between purlins when it is constrained. Sighting down a corrugated steel roof on a warm sunny day will show an undulating line compared to a straight line when the roof is cool. The forces created by expansion and contraction are self-levelling, i.e., each component moves under load until the resisting force is more than the expansion force.
- When a length of sheeting is solid fastened at the centre and unconstrained at either end, the movement is towards the ends of the sheeting; meaning the actual expansion or contraction movement is only half that of a full length of roof or wall cladding fastened at one end. Special design of the ridge or head barge flashing is required in these cases to allow free movement. Alternatively, sheets can be solidly fixed at the upper region, so all expansion takes place in the lower part of the sheet towards the eaves.
Notes:
- Roofs requiring oversized holes are solid fixed towards the ridge and provision for expansion is made towards the gutter line.
- These are guidelines only and special engineering of the roof, fixing or ventilation may allow greater spans to be used.
- These diagrams refer only to roof cladding screwed through the top. Secret or clip-fixed roofs can move more freely if installed correctly and allow for greater run lengths.
- The recommendations are based on preventing damage to the fasteners and are not recommendations to prevent roof noise.
End laps should be avoided if possible when installing metal roof cladding as an incorrectly sealed end lap may entrap water and cause corrosion. When the sheets are too long to be transported or exceed the longest recommended length (see 7.3.2 Roof Cladding Expansion Provisions), the transverse or end lap joint can be avoided by using a waterfall step. (See 8.5.5.3A Step Apron Details)
When long lengths outside the capacity of available transport are required, secret-fixed roof cladding can be supplied by using an onsite roll-forming machine.
Where end laps are unavoidable, a sealed joint should be made using sealant at both ends of the lap. The upper seal is critical as condensation entering the upper side of the lap from underneath can cause rapid corrosion. (See 14.12.1 Sealing End Laps.) Rivets are used to fix the sheets together and should not be fastened to the purlin. The sheets are fixed to the purlin using screw fixings.
The two lengths should be regarded as one length for expansion provisions.
As with roofing, wall cladding sheets should, wherever possible, be laid in a single continuous length. Where this is not feasible due to excessive length or other constraints, there are options for lapping.
When the internal environment is dry and the wall is unlined, sheets can be simply end-lapped by approximately 150 mm. In dwellings, lined buildings, and buildings with moist internal environments, the laps should be sealed at both ends as per roof laps. The downside of end lapping is that there are four layers of material at the side lap/end lap junction. This often leads to an untidy looking join.
The preferred option where aesthetics must be considered is not to end-lap the sheets, but to have a zed flashing under the upper sheet and over the lower, with cover as shown in 8.4F Barge Flashing Cover — Trapezoidal and Secret Fixed Table and 8.4J Transverse Apron Flashing Cover Table. This is both tidier and allows the sheets to thermally expand individually.