Rainwater Heads

Rainwater heads must be at least as wide as the gutter and have an overflow (normally a weir type). The cross-sectional area of the overflow must be at least equal to that of the required downpipe size for the catchment being served. The lower edge of the overflow must be at least 25 mm below the sole of the gutter, and the upper edge must be at least 25 mm below the upper edge of the gutter.
Clause: 
005_006_001_000_000_000_000_000_000
Clause Number: 
5.6.1
/cop/roof-drainage/rainwater-heads-sumps-and-overflows#rainwater-heads
Revision Category: 
1 - Minor Errata
Revision Detail: 

Punctuation fix.