Standing Seam Roofing Wind Loads

Clip spacings for proprietary tray roofing must be set out as per the manufacturer's data for the design wind load of the building.

 

Generic Standing Seam Clip Spacing

Rib HeightMax Pan WidthNZS 3604 Wind Zone
  MediumHighVery HighExtra High
25 mm300 mm500 mm500 mm500 mm500 mm
400 mm500 mm500 mm500 mm500 mm
500 mm400 mm400 mm400 mmN/A
32 mm300 mm600 mm600 mm600 mm600 mm
400 mm600 mm600 mm600 mm600 mm
520 mm600 mm600 mm600 mm400 mm
38 mm300 mm600 mm600 mm600 mm600 mm
400 mm600 mm600 mm600 mm600 mm
500 mm600 mm600 mm600 mm400 mm
 


 

Clause: 
015_004_009_000_000_000_000_000_000
Clause Number: 
15.4.9
/cop/other-products/tray-roofing#standing-seam-roofing-wind-loads
Revision Category: 
2 - Editing and rearrangement
Revision Detail: 

Renamed table, it is now called: Generic Standing Seam Clip Spacing and inserted Medium Wind Zone.