Pullout resistance for different constructions

Pullout resistance in kN required for battens for buildings with ceilings

cpe = -0.9, cpi = 0, cp = 0.9

Purlin/ batten sizeMax spanWind Zone 0.61kPaWind Zone 0.61kPaWind Zone 0.82kPaWind Zone 0.82kPaWind Zone 1.16kPaWind Zone 1.16kPaWind Zone 1.50kPaWind Zone 1.50kPa
mm x mmmmLow 32m/sLow 32m/sMedium 37m/sMedium 37m/shigh 44m/shigh 44m/sVery high 50m/sVery high 50m/s
  MPMPMPMP
50 x 409000.20.30.30.40.30.50.50.7
50 x 5012000.20.40.30.50.50.70.60.9
M = main body of the roof P = periphery

 

Pullout resistance in kN required for buildings without ceilings (but with a permeable
windward wall)

cpe = -0.9, cpi = 0.2, cp = 1.1

Purlin/ batten sizeMax spanWind Zone 0.61kPaWind Zone 0.61kPaWind Zone 0.82kPaWind Zone 0.82kPaWind Zone 1.16kPaWind Zone 1.16kPaWind Zone 1.50kPaWind Zone 1.50kPa
mm x mmmmLow 32m/sLow 32m/sMedium 37m/sMedium 37m/shigh 44m/shigh 44m/sVery high 50m/sVery high 50m/s
  MPMPMPMP
50 x 409000.20.30.30.50.40.60.60.8
M = main body of the roof P = periphery

 

 

Pullout resistance in kN required for buildings without ceilings (and with a dominant
windward opening)

cpe = -0.9, cpi = 0.8, cp = 1.7

Purlin/ batten sizeMax spanWind Zone 0.61kPaWind Zone 0.61kPaWind Zone 0.82kPaWind Zone 0.82kPaWind Zone 1.16kPaWind Zone 1.16kPaWind Zone 1.50kPaWind Zone 1.50kPa
mm x mmmmLow 32m/sLow 32m/sMedium 37m/sMedium 37m/shigh 44m/shigh 44m/sVery high Very high 50m/s 50m/s 
  MPMPMPMP
50 x 409000.40.50.50.70.710.91.3
50 x 5012000.50.70.60.90.91.31.11.7
M = main body of the roof P = periphery

 

Tile Batten Fastener Requirements

FastenerSizeNo.kN
Gun nail90 x 3.1510.4
Ringshank nail (gun/hand)90 x 3.210.6
Gun nail90 x 3.1520.7
Twist Shank Nail90 x 3.310.9
Purlin Screw c/s head10g x 10012.5
Type 17 screw14g x 10017.3