Flashing Laps
Laps in flashings should comply with the following criteria:
- Water must flow over a lap, not into it,
- a lap must not rely solely on sealant,
- sealed laps must be mechanically fixed at 50 mm centres,
- unsealed laps must have a minimum cover of 150 mm, and
- a minimum of 100 mm cover is recommended for sealed laps to facilitate the correct alignment of two flashings.