Minimum Freeboard Values
In gutters where overflow can enter the structure, it is necessary to have freeboard to allow for wave action, obstructions, and other unforeseen circumstances. Capacity Calculations allow for these minimum freeboard values.
Minimum Freeboard Values
Gutter Type | Freeboard |
---|---|
Internal gutters | 30 mm |
Secret gutters | 15 mm |
Valleys > 8° | 15 mm |
Valleys < 8° | 20 mm |
Asymmetrical valleys | 20 mm |
External Gutters with Overflow | No freeboard required |
External gutters with no overflow | 15 mm |
Clause:
005_003_003_000_000_000_000_000_000
Clause Number:
5.3.3
/cop/roof-drainage/roof-drainage-design#minimum-freeboard-values
Revision Category:
3 - Substantial change to recommendation