Material Selection
Note: this is the minimal requirement to achieve compliance with NZBC Clause B2-Durabilty. Meeting the minimum requirements of NZBC clause B2 Durability does not necessarily represent optimal product selection. In a transition zone, it may be more cost effective over the life cycle of the building, and for meeting customer expectations, to choose a more durable option.
Material Selection : Exposed Roofs and flashing
Durability Required : 15 years
Marine Zone | Exposed Fastener Class (minimum) | Acceptable Materials | |
---|---|---|---|
***As defined by AS/NZS 2728. | |||
B: Moderate Inland | C4 |
| |
C: Moderate Marine | C4 |
| |
D: Severe Marine | C4 |
| |
E: Very Severe Marine | C5 |
| |
F: Extreme Marine | C6 |
|
Material Selection : Walls*, fascias and sheltered roofs and flashings
Durability Required : 15 years
Marine Zone | Exposed Fastener Class (minimum) | Acceptable Materials | |
---|---|---|---|
*The practicality of carrying out regular maintenance, and difficulty of replacement, should also be considered when considering wall cladding material options. | |||
***As defined by AS/NZS 2728. | |||
B: Moderate Inland | C4 |
| |
C: Moderate Marine | C4 |
| |
D: Severe Marine | C4 |
| |
E: Very Severe Marine | C5 |
| |
F: Extreme Marine | C6 |
|
Material Selection : Flashings Behind Cladding
Durability Required : 50 years
Marine Zone | Acceptable Materials | |
---|---|---|
**Stainless steel must not be in wet contact with metallic coated steel, plain or painted. | ||
***As defined by AS/NZS 2728. | ||
B: Moderate Inland |
| |
C: Moderate Marine |
| |
D: Severe Marine |
| |
E: Very Severe Marine |
| |
F: Extreme Marine |
|
Clause:
004_006_003_000_000_000_000_000_000
Clause Number:
4.6.3
4.6.3